UL 508A

Original price was: $897.00.Current price is: $448.00.

Industrial Control Panels

Underwriters Laboratories , 04/24/2018

Category:
Please note: All interim revisions for this edition available at time of your purchase will be included.

This New Edition of UL 508A includes the following changes in requirements:

Interlocking means to prevent restoring power

Marking of Overload Setting

SB4.3.1 correction

Redefining the definition of Low Voltage

Cable Assemblies and Fittings for Power and Control Circuits

SB4.2.3 Exception No. 4 – Substituting for a Non-Current Limiting Overcurrent Device

Add 6P as an additional device that may be used to close an opening in a Type 4X enclosure in UL 508A, Table 19.2

Original price was: $283.55.Current price is: $141.00.

Industrial Control Panels

Underwriters Laboratories , 12/20/2013

Category:
Please note: All interim revisions for this edition available at time of your purchase will be included.

Industrial Control Panels

UL 508A

1 Scope

1.1 These requirements cover industrial control panels intended for general industrial use, operating from a voltage of 600 volts or less. This equipment is intended for installation in ordinary locations, in accordance with the National Electrical Code, ANSI/NFPA 70, where the ambient temperature does not exceed 40°C (104°F) maximum.

1.2 These requirements also cover industrial control panel enclosures and industrial control panels intended for flame safety supervision of combustible fuel type equipment, elevator control, crane or hoist control, service equipment use, marine use, air conditioning and refrigeration equipment, and for control of industrial machinery including metalworking machine tools, power press controls, and plastic injection molding machinery.

1.3 This equipment consists of assemblies of two or more power circuit components, such as motor controllers, overload relays, fused disconnect switches, and circuit breakers, or control circuit components, such as pushbuttons, pilot lights, selector switches, timers, and control relays, or a combination of power and control circuit components, with associated wiring, and terminals . These components are mounted on, or contained within, an enclosure, or are mounted on a sub-panel.

1.4 An industrial control panel does not include an evaluation of the controlled equipment such as motors, heaters, lighting, and other loads connected to power circuits. Unless specifically noted on the wiring diagram of the industrial control panel, an industrial control panel does not include equipment mounted remotely from the panel and connected via a wiring systems or equipment field installed on or within the industrial control panel.

1.5 An evaluation of the adequacy of the controls and protective devices contained in an industrial control panel for supervision and proper functioning of the controlled loads or equipment is not covered by the requirements in this standard. Such evaluations are covered by the standards applicable to the complete piece of utilization equipment.

1.6 The evaluation of a pre-fabricated building, structure, or platforms supplied with industrial control panels are not covered by the requirements in this standard.

1.7 Fire pump controllers are covered by the Standard for Fire Pump Controllers, UL 218.

1.8 Equipment intended for use in hazardous locations, as defined in the National Electrical Code, ANSI/NFPA 70, are covered by the Standard for Industrial Control Equipment for Use in Hazardous (Classified) Locations, UL 698.

1.9 Industrial control panels incorporating intrinsic safety barriers and intended for connection to circuits residing in hazardous locations are covered by the Standard for Industrial Control Panels Relating to Hazardous (Classified) Locations, UL 698A.

1.10 Motor control centers, including motor control center sections and units, or equipment intended for field installation into a motor control center are covered by the Standard for Motor Control Centers, UL 845.

1.11 Assemblies of electrical control units or equipment containing electrical control units for fire-protective signaling systems are covered by the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864.

1.12 A freestanding assembly of circuit breakers and busses for control of electric light and power circuits or equipment intended for field installation in dead-front switchboards are covered by the Standard for Switchboards, UL 891.

1.13 Equipment intended to supply automatic illumination, power, or both, to critical areas and equipment essential to safety of human life is covered by the Standard for Emergency Lighting and Power Equipment, UL 924.

Original price was: $227.92.Current price is: $113.00.

Industrial Control Panels

Underwriters Laboratories , 01/01/2001

Category:
These requirements cover industrial control panels intended for general industrial use, operating from a voltage of 600 volts or less. This equipment is intended for installation in ordinary locations, in accordance with the National Electrical Code, ANSI/NFPA 70, where the ambient temperature does not exceed 40C (104F) maximum.

These requirements also cover industrial control panel enclosures and industrial control panels intended for flame safety supervision of combustible fuel type equipment, elevator control, crane or hoist control, service equipment use, marine use, air conditioning and refrigeration equipment, and for control of industrial machinery including metalworking machine tools, power press controls, and plastic injection molding machinery.

This equipment consists of assemblies of two or more components, such as motor controllers, overload relays, fused disconnect switches, circuit breakers, and related control devices such as pushbuttons, pilot lights, selector switches, timers, control relays, and similar devices, with associated wiring, terminal blocks, and similar components.

Fire pump controllers are covered by UL 218, Standard for Fire Pump Controllers.

Equipment intended for use in hazardous locations, as defined in the National Electrical Code, ANSI/NFPA 70, are covered by UL 698, Standard for Industrial Control Equipment for Use in Hazardous (Classified) Locations.

Industrial control panels incorporating intrinsic safety barriers and intended for connection to circuits residing in hazardous locations are covered by UL 698A, Standard for Industiral Control Panels Relating to Hazardous (Classified) Locations.